Product Model | Rated voltage KV | Rated current A | 4s thermal stability current (effective value)KV | Dynamic stable current (effective value)KV | Full-wave impulse withstand voltage Relatively(KV) | Full-wave impulse withstand voltage Interfracture(KV) | 1min power frequency voltageRelatively(KV) | 1min power frequency voltageInterfractur(KV) |
HGW9-12/200 | 12 | 200 | 12500 | 31500 | 75 | 85 | 38 | 42 |
HGW9-10/400 | 12 | 400 | 12500 | 31500 | 75 | 85 | 38 | 42 |
HGW9-10/630 | 12 | 630 | 20000 | 50000 | 75 | 85 | 38 | 42 |